| Supply voltage |
100 to 240 VAC |
24 VAC/VDC |
| Operating voltage range |
85% to 110% of the rated supply voltage |
Power consumption
(under maximum load) |
6 VA max. |
4.5 VA max. (24 VAC)
4.5 W max. (24 VDC) |
| Insulation resistance |
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply. |
| Dielectric strength |
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply. |
| Noise immunity |
±1,500 V on power supply terminals in normal or common mode.
±1 μs, or 100 ns for square-wave noise with 1 ns. |
±480 V on power supply terminals in normal mode.
±1,500 V in common mode.
±1 μs, or 100 ns for square-wave noise with 1 ns. |
| Vibration resistance |
Vibration: 10 to 55 Hz, 0.35-mm half amplitude
5 min each in X, Y, and Z directions for 10 sweeps. |
| Shock resistance |
150 m/s² (100 m/s² for relay contact outputs) 3 times each on 3 axes, 6 directions. |
| Ambient temperature |
Operating: -10°C to 55°C (with no condensation or icing)
Storage: -25°C to 65°C (with no condensation or icing) |
| Ambient humidity |
Operating: 25% to 85% (with no condensation) |
| Approved safety standards |
UL61010-1, CSA C22.2 No.61010-1-04, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection) |
| EMC |
| (EMI) |
EN61326-1 Industrial electromagnetic environment |
| Emission Enclosure: |
CISPR 11 Group 1 class A: CISRP16-1/-2 |
| Emission AC Mains: |
CISPR 11 Group 1 class A: CISRP16-1/-2 |
| (EMS) |
EN61326-1 Industrial electromagnetic environment |
| Immunity ESD: |
EN61000-4-2: 4 kV contact discharge / 8 kV air discharge |
| Immunity RF-interference: |
EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz) |
| Electrical Fast Transient Noise: |
EN61000-4-4: 2 kV (power line) |
| Immunity Burst Noise: |
1 kV line to line (I/O signal line) |
| Immunity Surge: |
EN61000-4-5: 1 kV (power line) / 2 kV line to ground (power line) |
| Immunity Conducted Disturbance: |
EN61000-4-6: 3 V (0.15 to 80 MHz) |
| Immunity Voltage Dip/Interrupting: |
EN61000-4-11: 0.5 cycle, 0, 180°, 100% (rated voltage) |
|
| Weight |