| Input Channels |
Four, single-ended, in addition to smart sensor data channels |
| Measurement Range and Accuracy |
0–25.6 mA DC, ±5 µA ± 0.15% of reading
0–2.5 V DC, ±0.25 mV ±0.2% of reading
0–5 V DC, ±0.25 mV ±0.2% of reading
0–10 V DC, ±0.3 mV ±0.2% of reading
0–20 V DC, ±0.6 mV ±0.2% of reading
0–33 V DC, ±1.20 mV ±0.2% of reading |
| Resolution |
15 bits |
| Field Wiring |
Two- or three-wire via screw terminals, 16–24 AWG |
| Minimum/Maximum Input Voltage |
0/33 V DC |
| Minimum/Maximum Input Current |
0/25.6 mA |
| Minimum Source Impedance for Current Measurement |
20 KΩ |
| Excitation Voltage |
12 V DC ±5% at 200 mA maximum per module |