| Item |
Specification |
| NJ501-□□□□ |
NJ301-□□□□ |
NJ101-□□□□ |
| Enclosure |
Mounted in a panel |
| Grounding Method |
Ground to less than 100 Ω |
| Dimensions (height×depth×width) |
90 mm × 90 mm × 90 mm |
| Weight |
550 g (including the End Cover) |
| Current Consumption |
5 VDC, 1.90 A (including SD Memory Card and End Cover) |
| Operation Environment |
Ambient Operating Temperature |
| 0 to 55°C |
| Ambient Operating Humidity |
| 10% to 90% (with no condensation) |
| Atmosphere |
| Must be free from corrosive gases. |
| Ambient Storage Temperature |
| -20 to 75°C (excluding battery) |
| Altitude |
| 2,000 m or less |
| Pollution Degree |
|
2 or less: Meets IEC 61010-2-201. |
|
Noise Immunity |
|
2 kV on power supply line (Conforms to IEC 61000-4-4.) |
|
Overvoltage Category |
|
Category II: Meets IEC 61010-2-201. |
|
EMC Immunity Level |
|
Zone B |
|
Vibration Resistance |
|
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s² for 100 min in X, Y, and Z directions
(10 sweeps of 10 min each = 100 min total) |
|
Shock Resistance |
|
Conforms to IEC 60068-2-27.
147 m/s², 3 times in X, Y, and Z directions
(100 m/s² for Relay Output Units) |
| Battery |
Life *1 |
| 5 years at 25°C |
|
Model |
|
CJ1W-BAT01 |
| Applicable Standards *2 |
cULus, EU, UKCA, RCM, KC, NK, LR *3 |