| Item |
|
NX1P2-□ CPU Unit |
| Enclosure |
|
Mounted in a panel |
| Grounding |
|
Less than 100 Ω |
| Operation environment |
Ambient operating temperature |
0 to 55°C |
| Ambient operating humidity |
10% to 95% (with non condensation) |
| Atmosphere |
Must be free from corrosive gases |
| Ambient storage temperature |
–25 to 70°C (excluding battery) |
| Altitude |
2,000 m or less |
| Pollution degree |
2 or less: Conforms to JIS B3502 and IEC 61131-2. |
| Noise immunity |
2 kV on power supply line (conforms to IEC 61000-4-4.) |
| Overvoltage category |
Category II: Conforms to JIS B3502 and IEC 61131-2 |
| EMC immunity level |
Zone B |
| Vibration resistance |
Conforms to IEC 60068-2-6
5 to 8.4 Hz with 3.5 mm amplitude, 8.4 to 150 Hz.
Acceleration of 9.8 m/s² for 100 min in X, Y and Z directions
(10 sweeps of 10 min each = 100 min total) |
|
Shock resistance |
Conforms to IEC 60068-2-27
147 m/s², 3 times in X, Y and Z directions |
| Battery |
Life |
5 years at 25°C |
| Model |
CJ1W-BAT01 (sold separately) |
| Applicable standards |
EU Directives |
EN 61131-2 |
| cULus |
Listed UL 61010-2-201 and ANSI/ISA 12.12.01 |
| Others |
KC |